Solberg Paper High Efficiency Series Filter Elements
HEPA (HE): Media is 99.97% removal efficiency at 0.3 micron
ULPA (UL): Ultra High Efficiency Media, 99.995% removal efficiency at 0.1 micron. Contact for availability.
PTFE (TF): Chemical Resistant and Moisture Resistant Media, 99.5% removal efficiency 0.3 micron
Features
HEPA
- Media Classification: E12
- 99.97% removal efficiency standard at 0.3 micron
- Temp (continuous): min -15°F (-26°C) max 220°F (104°C)
- Heavy duty industrial strength glass surrounded by heavy gauge expanded metal
ULPA
- Media classification: H14
- 99.995% removal efficiency standard at 0.1 micron
- Temp min: -15°F (-26°C), max: 220°F (104°C)
TF
- Media classification: E11
- 99.5% removal efficiency standard at 0.3 micron
- Chemical & moisture resistant media
- Temp (intermittent): 220°F (104°C)
Applications
HEPA
- Power Plants
- Pneumatic Conveying Systems
- Pharmaceutical Industry
- Please see canister applications
ULPA
- Vacuum Pumps & Systems
- Laboratory Industry
- Hospital Vacuum Units
- Medical gas distribution systems (Certified by independent testing)
TF
- Cement
- Pharmaceutical Industry
- Semiconductor Industry
- Food Processing
- Coal handling
Options
- Polyester/Paper Media with SS ID/OD, J Series (select sizes)
- Polyester/Paper Media with SS ID/OD, Food Grade Silicone Endcaps, K Series (select sizes)
- Polyester/Paper Media with SS ID/OD/EC, Q Series (select sizes)
- Polyester/Paper Media with SS ID/OD/EC, Silicone Endcap Adhesive, R Series (select sizes)
- Atex Certification (select models)
- Various gaskets or potting compounds
HEPA
- Silicone potting, Viton gaskets
ULPA
- Silicone potting, Viton gaskets
TF
- Viton gaskets, epoxy potting
Endcap Styles
- B = Closed one end with bolt hole, open on other end
- C = Closed one end, open on other end
- G = Galvanized metal
- M = Molded plastisol
- N = Neoprene blended gasket on open endcaps
- R = Mixed rubber/cork gasket on open endcaps
- W = Wrapped coalescing media